|CMP|FPLP|CL3P|CL2P|CMR|FPLR|CL3R|CL2R|CM|FPL|CL3|PLTC|CL2|CMX|CL3X|CL2X|
CMP X
FPLP X X
CL3P X X X
CL2P X X X X
CMR X X X X X
FPLR X X X X X X
CL3R X X X X X X X
CL2R X X X X X X X X
CM X X X X X X X X X
FPL X X X X X X X X X X
CL3 X X X X X X X X X X X
PLTC X X X X X X X X X X X X
CL2 X X X X X X X X X X X X X
CMX X X X X X X X X X X X X X X
CL3X X X X X X X X X X X X X X X X
CL2X X X X X X X X X X X X X X X X X
BASED ON 1987 NATIONAL ELECTRICAL CODE SUBSTITUTION CHART.
1. PLENUM CABLE must pass the modified Steiner Tunnel Tes-UL910.
2. RISER CABLE must pass UL1666 flame test.
3. GENERAL BLDG WIRING must pass UL1581 vertical tray flame test.
4. RESTRICTED USE must pass UL1581 VW-1 test.
This table courtesy of GEPCO International.