  1.  
  2. --------------------------------------------------------------------------
  3.      |CMP|FPLP|CL3P|CL2P|CMR|FPLR|CL3R|CL2R|CM|FPL|CL3|PLTC|CL2|CMX|CL3X|CL2X|
  4.  
  5. CMP    X
  6. FPLP   X    X
  7. CL3P   X    X   X
  8. CL2P   X    X   X    X
  9. CMR    X    X   X    X    X
  10. FPLR   X    X   X    X    X   X
  11. CL3R   X    X   X    X    X   X    X
  12. CL2R   X    X   X    X    X   X    X     X
  13. CM     X    X   X    X    X   X    X     X   X
  14. FPL    X    X   X    X    X   X    X     X   X  X
  15. CL3    X    X   X    X    X   X    X     X   X  X  X
  16. PLTC   X    X   X    X    X   X    X     X   X  X  X    X
  17. CL2    X    X   X    X    X   X    X     X   X  X  X    X   X
  18. CMX    X    X   X    X    X   X    X     X   X  X  X    X   X    X
  19. CL3X   X    X   X    X    X   X    X     X   X  X  X    X   X    X    X
  20. CL2X   X    X   X    X    X   X    X     X   X  X  X    X   X    X    X   X
  21.  
  22. BASED ON 1987 NATIONAL ELECTRICAL CODE SUBSTITUTION CHART.
  23. 1.     PLENUM CABLE must pass the modified Steiner Tunnel Tes-UL910.
  24. 2.     RISER CABLE must pass UL1666 flame test.
  25. 3.     GENERAL BLDG WIRING must pass UL1581 vertical tray flame test.
  26. 4.     RESTRICTED USE must pass UL1581 VW-1 test. 
  27.  
  28. This table courtesy of GEPCO International.
  29.  
  30. via  AV-Sync (404) 320-6202
  31.